Absolute Humidity (AH) As the partial pressure exerted by each gas also represents the volume of each gas present (proportionally), then it follows that as the partial pressure exerted by water vapour increases, so the volume of water vapour present also increases. Absolute Humidity is the mass of water present in unit volume of moist air at a given temperature and pressure and is measured in grams per cubic metre of air (g/m³). Note that the term absolute humidity is often mistaken for mixing ratio or humidity ratio. Absolute humidity is not normally shown on a standard psychrometric chart. Water Activity (aw) An expression of the relative avalability of water in a particular food or substance. Pure water has a water activity of exactly 1.00 The water activity of a substance is expressed as one-hundredth of it’s relative humidity. Mixing Ratio or Humidity Ratio (w) Humidity Ratio defines the mass of water in the volume occupied by 1 kg of dry air. In other words it is the amount of water required to be evaporated into 1 kg of dry air in order to achieve a specific condition. Humidity Ratio is often expressed in grams of water per kilogram of dry air (g/kg). Note that there can be a significant difference between Mixing/Humidity Ratio and Absolute Humidity. Air conditioning engineers find Mixing/Humidity Ratio far more practical than Absolute Humidity. Unlike Absolute Humidity, Mixing/Humidity Ratio does not change with temperature (unless cooled below the dewpoint). Note that the term "Moisture Content" is often used instead of "Mixing or Humidity Ratio". This is now generally accepted within the HVAC industry. It is also used throughout this web site. Moisture Content is normally shown on a standard psychrometric chart (kg/kg of dry air). Specific Humidity (SH) The ratio of water vapour to air (dry air plus the water vapour) in a particular volume of air. Specific humidity is related to mixing ratio (and vice versa). This is not often used in psychrometric calculations. Dewpoint (°Cdp) As the mass of water vapour that air can hold is dependant on the air temperature (and pressure), if the air is cooled, the amount of water it can hold is reduced and the relative humidity subsequently rises. If air is cooled to the point where it becomes 100% saturated (pws), then any further cooling will cause moisture to deposit out of the air in the form of condensation or dew. The temperature at which this occurs is the dew point of the air. The dewpoint is the temperature below which water vapour in the air will start to condense. Even though dewpoint is expressed as a temperature, it is determined by the amount of water vapour in the air at a given pressure. Dewpoint is always less than or equal to the actual air temperature and, at normal atmospheric pressure, must always be between -273°C and 100°C. Dewpoint is not shown separately on a psychrometric chart as it relates directly to dry bulb or wet bulb temperatures. Sensible Heat May be defined as heat which when applied to (or removed from) a substance, causes only a change in temperature. Sensible heat is measured in joules per kilogram (J/kg). Latent Heat May be defined as heat which when applied to (or removed from) a substance, produces a change in state without any change to temperature. Latent heat is measured in joules per kilogram (J/kg). Enthalpy of humid gas (ht) Measure of the total energy in a humid gas. In other words, it is the sensible heat + the latent heat. Enthalpy is a useful concept in air conditioning where it is important to know how much of the "stored" energy will be consumed or released when the temperature or moisture content is raised or lowered. Enthalpy is measured in Joules per kilogram (J/kg) or more commonly kJ/kg. The reference point for enthalpy is completely dry air at a temperature of 0°C (0°C, 0%RH = 0 J/kg). Specific enthalpy is normally shown on a standard psychrometric chart (kJ/kg). Note that Joule is the SI unit of Energy. The rate of energy transfer is known as Power which is measured in J/s or watt (1 kJ/s = 1 kW). |